Mazhab-Jafari A, Akbari-Azirani A. Power Transformer Winding Modelling Using Multi-Conductor Transmission Line Model for Partial Discharge Localization. Journal of Iranian Association of Electrical and Electronics Engineers 2009; 6 (1) :73-83
URL: http://jiaeee.com/article-1-231-en.html
Abstract:   (4557 Views)

In this paper Multi conductor transmission line model (MTLM) was used for partial discharge (PD) localization in power transformers’ windings. The parameters of the model were computed considering practical issues of power transformer design. To decrease computational complexity of the model, two methods for calculation of model parameters were studied and the most suitable method was chosen based on comparison between measured and calculated transfer function of a 132kV/20kV transformer and a 420kV/15.75kV transformer. To investigate the accuracy of MTLM in PD localization, PD pulses generated by a PD calibrator were injected into different clamps of a research 20kV/0.4kV transformer and measured at both ends of the winding. The sectional winding transfer functions computed by the model were used to refer measured PD signals to possible PD locations. Then by comparison of referred signals, PD location in the winding was estimated.

Full-Text [PDF 611 kb]   (2796 Downloads)    
Type of Article: Research | Subject: Power
Received: 2017/02/22 | Accepted: 2017/02/22 | Published: 2017/02/22

Add your comments about this article : Your username or Email:
CAPTCHA

Rights and permissions
Creative Commons License This Journal is an open access Journal Licensed under the Creative Commons Attribution-NonCommercial 4.0 International License. (CC BY NC 4.0)

© 2025 CC BY-NC 4.0 | Journal of Iranian Association of Electrical and Electronics Engineers

Designed & Developed by : Yektaweb